4
PC6501 Remote Keypad
• Connects to control panel via 4-wire Combus
• Alphanumeric liquid crystal display
• Built-in piezoelectric buzzer
• Full annunciation of zones and system status
• Dimensions 5.5” x 4.5” x 1” deep (150 x 114 x 25 mm)
• Maximum current draw of 55mA (from Combus), 90mA with
backlighting boost.
• Up to 16 keypads on system
• Provides Tamper reporting codes
• Low Combus supervision to main board
PC6820 Access Control Module
Two Zone Inputs
• Two programmable supervised zones ( 5600Ω )
• Zones may be programmed as Standard, Force Arm Delay, or
Auxiliary Delay zone types
• Up to 16 PC6820 modules can be added (up to 32 access
points)
Non Volatile RAM (internal memory)
• Does not lose any system programming when the module is
powered down.
Low Current Outputs
• Six low current outputs (open collector outputs switched to
ground 25mA max.) :
• Two LED terminals - To the LED input of the reader
• Two BUZ terminals - To the buzzer input of the reader
• Two OUT terminals - Reserved for future use
Regulated Power Supply (1.5 Amp max.)
• Electronic shutdown protection of the battery, auxiliary
output, 5 and 12 V reader power supplies, and lock device
power output
• Auxiliary output supply: 12VDC, 125mA Max
• LK1 and LK2 Door Strike power: 12VDC, 250mA Max
• Reader Power 5VDC, 125mA Max
• Reader Power 12VDC, 125mA Max
Reader Technology
• Polaris, Shadow Prox, HID Proximity and 26-bit Standard
Wiegand format
Access Card Compatibility
• Polaris POL-C1CN - Polaris Magnetic Cards
• Shadow Prox, Module Numbers:
SH-C1 - Shadow Prox Card
SH-K1 - Shadow Prox Keytag
• HID Proximity:
HID-C1325KSF - Proximity Card
HID-C134KSP - Proximity Keytag
• Wiegand - Standard 26 bit formats
Battery
• 12V
DC 7.0Ah recommended rechargeable gel-cell
Transformer
• 16.5 VAC, 40VA
Operating Temperature
•2
°
C to 40
°
C (35
°
F to 110
°
F) operational temperature range
•90
°
non-condensing humidity
Output Voltage
• Output voltage = 13.8VDC (with normal AC and a fully
charged battery). Devices that require power from the
PC6820 should be capable of operation over the voltage
range of 10 to 14VDC.
• 5V Power Supply - Devices connected to the 5V supply should
be capable of operation between 4 and 6V.
PC6442, PC6443 Interface Modules
• 1.5Amp power supply
• Outputs for future use
• AUX current: 500mA
• 115 baud RS-232 communications
• Connects to control panel via 3-wire Backbone
• 1 module per system
WARNING: Standard Maxsys combus modules do not work on
the PC6010. Do NOT attempt to use these modules.