Programming Sections: 5.1 For the Record PWS Sect 1
17
5.1 For the Record PWS Sect 1
This Section identifies the Client, Installation Date, Installers Code, Hardware configuration and Programming summary for each zone. Remove
these pages and retain for reference.
5.2 Keypad Programming PWS Sect 2
Refer to Section 2.6 ‘Keypad Assignment’
5.3 Basic Programming PWS Sect 3
[001]-[004] - Zone Definitions
These sections require 16 two digit entries. Each two digit number entered determines how a zone will operate.
NOTE: In addition to selecting how each zone will operate, attributes may be programmed by zone (See Section 5.4 Advanced Programming
PWS Sect 4 [101-[164]).
[001]-[004] ZONE DEFINITIONS
Option Zone Type Description
00 Null Zone For zones that are not used and do not require a closed loop or EOL resistor
01 Delay 1 Follows the Entry Delay 1 and Exit Delay programmed in Section [005] and is normally used for Entry/Exit doors. The
exit delay starts as soon as the panel is armed. The zone may be opened and closed during the delay time without
causing an alarm. After the exit delay time has expired, opening the zone will start the Entry Delay timer. During the
Entry Delay time, the keypad buzzer will sound steadily to advise the user that the system should be disarmed. If the
panel is disarmed before the Entry Delay expires, no alarm will be generated.
02 Delay 2 Operates the same as Type [01] zone except the Entry Delay time can be independently set in Section [005]. The Exit
Delay time is common to both zone types.
03 Instant Normally used for door and window contacts and has the standard Exit Delay, but is instant when opened after the
Exit Delay expires
04 Interior Used with interior motion detectors. Interior zones feature an Exit Delay and an Entry Delay provided that any Delay
type zone has been tripped first. If the protected area is entered without coming through the a delayed entrance and
an Interior zone is tripped, an immediate alarm will be generated
05 Interior Stay/Away. If the system is armed and a Delay zone is NOT tripped during the exit delay time, this zone type will be bypassed. If
the [*][1] command is used to activate all Stay/Away type zones, this zone will have the standard exit delay. Once
armed, this zone will act like an Interior type zone [04].
06 Delay Stay/Away If the system is armed and a Delay zone is NOT tripped during the exit delay time, this zone type will be bypassed. If
the [*][1] command is used to activate all Stay/Away type zones, this zone will have the standard exit delay. Once
armed, this zone will follow the Entry Delay time for Entry Delay 1 when tripped.
07 Delayed 24 Hour Fire
(Hardwired)
Operates the same as the standard Fire zone, except the alarm memory and transmission by the communicator is
delayed by 30 seconds. If the alarm is acknowledged by pressing any key within 30 seconds, the bells will silence and
the transmission will be aborted. If the alarm has been acknowledged, and the smoke detector has not been
restored to normal, the bell output will activate after 90 seconds, the user then has another 30 second delay before
the bell output latches and communications is activated. A code is then required to silence the bell output.
NOTE: The Fire Delay will be terminated if a 2nd Fire zone is tripped or if the [F] key is pressed during a delay.
08 Standard 24 Hour Fire
(Hardwired)
On alarm, the bell output will sound to indicate that the fire loop has been activated. If enabled, the communicator
will immediately transmit the alarm to the monitoring station.
NOTE: DO NOT change the Zone Attributes of Fire type zones from the default settings.
09 24 Hour Supervisory This zone is active at all times and will report an alarm at all times. The Supervision Options (NC, EOL, DEOL, ZD) do
not affect the functionality of the zone.
NOTE: This zone type must not be used for wireless zones.
10 24 Hour Supervisory
Buzzer
This zone is active at all times and will report an alarm at all times. Once tripped, the keypad buzzer will sound until
a valid access code is entered.
NOTE: This zone type should not be used on a Keyswitch ONLY system
11 24 Hour Burglary This zone is active at all times and will report an alarm if the panel is armed or disarmed. This zone will sound the bell
for the length of ‘Bell cutoff’ if the audible attribute is enabled.
12 24 Hour Holdup Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute.
13 24 Hour Gas Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute
14 24 Hour Heat Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute.
15 24 Hour Medical Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute.
16 24 Hour Panic Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute.
17 24 Hour Emergency Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute.
18 24 Hour Sprinkler Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute.
19 24 Hour Water Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute.
20 24 Hour Freeze Similar to 24 Hour Burglary except for System Event output type, SIA identifier and zone attribute.
21 24 Hour Latching
Tamper.
This zone type, when violated, will cause arming of the system to be inhibited until the valid Installer code is entered.
If this zone type is violated, the Installers code must be entered ([*][8] Installers Code) before the system can be
armed.
22 Momentary Keyswitch
Arm.
A keyswitch module may be connected to the zone programmed as Momentary Keyswitch arm. Momentary activa-
tion of this zone to the alarm state will alternatively arm and disarm the system and silence alarms.
NOTE: The keypad will not display an indication when this type of zone is activated.
23 Maintained Keyswitch
Arm
A Normally Open Keyswitch module may be connected to the zone programmed as Maintained Keyswitch arm. In
the restored state, the panel is disarmed. Only the violation of this zone type to the alarm state will make the panel
arm.