P R O G R A M D E S C R I P T I O N S
39
5.29 On-Site Printer
The panel, with the addition of the PC5400 printer module, will print all events as they occur to a local, on-
site serial printer. All events printed will include the time, date, partition and the event.
If a problem develops with the printer, such as power loss or paper outage the panel will store events until
the problem is corrected, at which point it will print the events from the buffer. The panel can store up to
128 events if such a condition occurs.
PC5400 Programming ............................................ Section [801]
5.30 Audio Interface Module
The PC5928 Audio Interface will allow you to connect up to 7 Interior (PC5921) or exterior (PC5921EXT)
Intercom Stations. These attractive, surface mount stations contain both speaker and microphone and will
allow you to add intercom features to your alarm system such as:
• Page/Answer • Do Not Disturb • Baby Listener Broadcast
• Answer Incoming Calls • Doorbell Function • Background Music
In addition to these features the module also has the Listen-in feature for central station monitoring. The
central station can select the audio station, listen/talk, extend on-line time and hang up. The Listen-In
feature can be enabled separately for telephone numbers 1/3 and 2.
For more information regarding the PC5928 Audio Interface Module refer to the Installation Manual for the product.
PC5928 Programming ............................................ Section [802]
Phone 1 & 3 Listen-In Enabled .............................. Section [381], Option 5
Phone 2 Listen-In Enabled ..................................... Section [381], Option 6
5.31 Default (Factory)
On occasion it may be necessary to default the main control panel or one of the modules that can be
connected. There are several different defaults available including defaulting the main control panel,
Escort5580 module, PC5132 Wireless Expander Module, PC5400 Printer module and LINKS2X50 module.
Note: Defaulting the main panel does not default the keypads. Please refer to “Programming
LCD5500Z Keypads” in the Programming Worksheets for defaulting the LCD5500Z. PC55XXZ LED
keypads must be manually reprogrammed in installers section [000].
5.31.1 Factory Default Main Panel (Hardware)
Step 1 - Remove AC and battery from the panel.
Step 2 - Remove all wires from the Zone 1 and PGM1 terminals.
Step 3 - With a piece of wire short the Zone 1 terminal to the PGM1 terminal.
Step 4 - Apply AC power to the main panel.
Step 5 - When Zone Light 1 is lit on the keypad the default is complete.
Step 6 - Remove AC power from the control
Step 7 - Reconnect all original wiring and power up the control.
AC power must be used to power the panel. The panel will not default if the battery is used.
5.31.2 Factory Default Main Panel (Software) and other Modules
Step 1 - Enter the Installer Programming mode. Step 3 - Enter the Installer Code.
Step 2 - Enter Program Section [XXX]. Step 4 - Enter Program Section [XXX] again.
The panel will take a few seconds to perform the default. When the keypad is again operational the default
is complete.
Restore LINKS2X50 to Factory Default Programming ........................ Section [993]
Restore PC5100 to Factory Default Programming .............................. Section [994]
Restore Escort5580 to Factory Default Programming ......................... Section [995]
Restore PC5132 to Factory Default Programming .............................. Section [996]
Restore PC5400 to Factory Default Programming .............................. Section [997]
Restore PC5928 to Factory Default Programming .............................. Section [998]
Restore Main Panel (Software) to Factory Default Programming ....... Section [999]