
Program Descriptions
22
S E C T I O N 5
The following section explains all the programmable features including how the feature operates, options that
pertain to the feature and a summary of program locations that require programming.
5.1 Zone Definitions
These sections will allow you to select how each of the 32 zones will operate. Each zone requires a 2 digit entry.
In addition to selecting how each zone will operate, attributes may be programmed by zone (See
Section 5.2 “Zone Attributes”).
[00] Null Zone The zone will not operate in any way. Zones that are not used should be programmed as Null zones.
[01] Delay 1 Zone If this zone is violated when the panel is armed it will provide entry delay. The keypad buzzer
will sound to warn the user that the system must be disarmed. If the panel is not disarmed before the entry
delay expires an alarm will be generated. Typically this type of zone will be used for the front door, back
door or any other entry/exit point. Refer to Section [005], “System Times”, to program the Delay 1 zone
entry delay time.
[02] Delay 2 Zone This zone type operates the same as the Delay 1 zone option but can provide a different entry
delay. Typically this zone will be used for a garage door. Refer to Section [005], “System Times”, to program the
Delay 2 zone entry delay.
[03] Instant Zone If this zone type is violated when the panel is armed it will cause an instant alarm. Typically this
zone is used for windows, patio doors or other perimeter type zones.
[04] Interior Zone If this type of zone is violated when the panel is armed it will provide entry if a delay type zone
was violated first. Otherwise it will cause an instant alarm. Typically this zone is used for interior protection
devices, such as motion detectors.
[05] Interior Stay / Away Zone This zone type works the same as the Interior zone type with one exception. The
zone will be automatically bypassed under the following conditions:
• the panel is armed in the Stay Mode
(See Section 3.5 “Function Keys”)
• the panel is armed without entry delay
(See Section 3.4 “[
✱
] Commands, [
✱
] [9]”)
• the panel is armed with an access code and during the exit delay a Delay type zone is NOT tripped
The automatic bypass avoids having the user manually bypass interior type zones when arming at home. If
automatically bypassed, the user can reactivate the zones by entering the [✱][1] command
(See Section 3.4
“[
✱
] Commands, [
✱
][1] Zone Bypass”)
. Typically this zone is used for interior protection devices, such as motion
detectors. Stay/Away zones should not be programmed as global zones.
[06] Delay Stay / Away Zone This zone type will operate the same as the Interior Stay / Away zone type except that it
will always provide entry delay. Typically this zone is used for interior protection devices, such as motion
detectors and will help prevent false alarms since it will always provide the user the entry delay time to turn off
the panel. Stay/Away zones should not be programmed as global zones.
[07] Delayed 24 Hour Fire Zone If this zone is violated the alarm output will immediately activate but the
communicator will be delayed for 30 seconds. If during the 30 second delay the user presses any key on any
keypad the alarm output and communicator will be delayed an additional 90 seconds, providing the user time to
correct the problem. If after the 90 second delay the zone is still violated the process will begin again; the alarm
output will be activated but the communication will be delayed 30 seconds.
If the user does not press a key, after 30 seconds the alarm output will latch and the panel will communicate. The
alarm will sound for the Bell Cutoff time programmed in
Section [005],
or can be programmed to sound until a valid
code is entered,
Section [014], Option [8]”
.
PGM outputs programmed as [10] “Latched System Event” will only activate after the Delayed 24 Hour
Fire zone has latched.
If a second Fire type zone is violated or the Fire keys are pressed during the delay time the panel will
latch the alarm output and communicate immediately.
Do not wire Fire zones on keypad zone terminals if the DEOL supervision option is enabled for the
panel (section [013], option [2]).
If a delayed Fire zone is violated it will be displayed on all keypads and can be delayed at any keypad. Typically
this zone is used for latching smoke detectors.
[08] Standard 24 Hour Fire Zone When violated the panel will immediately latch the alarm output and communicate to
central station. The alarm will sound for the Bell Cutoff time programmed in
Section [005],
or can be programmed to
sound until a valid code is entered,
Section [014], Option [8]”
.
If a Fire zone is violated it will be displayed on all keypads. Typically this zone is used for pull stations.
Do not wire Fire zones on keypad zone terminals if the DEOL supervision option is enabled for the
panel (section [013], option [2]).
[09] 24 Hour Supervisory Zone If this zone is violated, whether armed or disarmed, the panel will report to the
central station, and log the zone fault.
Kommentare zu diesen Handbüchern