DSC PC6010 Installationshandbuch

Stöbern Sie online oder laden Sie Installationshandbuch nach Sicherheitszugriffskontrollsysteme DSC PC6010 herunter. DSC PC6010 Installation manual [en] Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - Programming Manual

Programming ManualPC6O1O Software Version 2.O

Seite 2

8SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA DLS SECTIONDLS SECTIONDLS SECTIONDLS SECTIONDLS SECTIONOther DLS Prog

Seite 3 - Introduction

9SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA COMMUNICATORCOMMUNICATORCOMMUNICATORCOMMUNICATORCOMMUNICATOR

Seite 4 - Main Programming Sections

10There are 2 formats in the PC6010 for communicating with the central station: SIA and Contact ID. Thesystem must be programmed to use the same commu

Seite 5 - Installer Options

11This section determines which reporting codes are sent to the selected telephone number. All reportingcodes can be programmed to communicate to any

Seite 6 - System Options

12SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA COMMUNICATORCOMMUNICATORCOMMUNICATORCOMMUNICATORCOMMUNICATOR

Seite 7 - System Times

13PH 1-2 BACKUPPH 1-2 BACKUPPH 1-2 BACKUPPH 1-2 BACKUPPH 1-2 BACKUPNNNNNPH 1-3 BACKUPPH 1-3 BACKUPPH 1-3 BACKUPPH 1-3 BACKUPPH 1-3 BACKUPNNNNNPH 2-3 B

Seite 8 - Zone Supervision

14SET CYCLE DAYSSET CYCLE DAYSSET CYCLE DAYSSET CYCLE DAYSSET CYCLE DAYS(0)(0)(0)(0)(0)SET 24HR TIMESET 24HR TIMESET 24HR TIMESET 24HR TIMESET 24HR TI

Seite 9 - Download Section

15PC6216 16 PC6216 16 PC6216 16 PC6216 16 PC6216 16 O/O/O/O/O/PPPPP(3)(3)(3)(3)(3)PC6108 ZONE EXPPC6108 ZONE EXPPC6108 ZONE EXPPC6108 ZONE EXPPC6108 Z

Seite 10 - Other DLS Programming

16PC6216 16 PC6216 16 PC6216 16 PC6216 16 PC6216 16 O/O/O/O/O/PPPPP(3)(3)(3)(3)(3)PC6108 ZONE EXPPC6108 ZONE EXPPC6108 ZONE EXPPC6108 ZONE EXPPC6108 Z

Seite 11 - Communicator Section

17SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA COMMUNICATORCOMMUNICATORCOMMUNICATORCOMMUNICATORCOMMUNICATOR

Seite 13

18•TLM Restoral - If there is a telephone line trouble, the PC6010 will not be able to communicate with thecentral station until the telephone line is

Seite 14 - Communicator Toggles

19SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA COMMUNICATORCOMMUNICATORCOMMUNICATORCOMMUNICATORCOMMUNICATOR

Seite 15

20These section options are relevant to the LINKS1000 operation.NOTE: Dial Tone Search must be included in the land phone number. See ‘Main Item’ for

Seite 16 - Test Code Transmission

21SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA SW AUX OUTPUTSW AUX OUTPUTSW AUX OUTPUTSW AUX OUTPUTSW AUX OUTPUTSYS

Seite 17 - Reporting Codes

22SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA PGM OUTPUTSPGM OUTPUTSPGM OUTPUTSPGM OUTPUTSPGM OUTPUTSMain PGM1 and

Seite 18

23PGM Pulse TimesThis section will allow you to select the amount of time a programmable output will remain active, afterbeing triggered.NOTE: The sys

Seite 19

24The output will activate when any fire or zone alarm occurs on any of the selected areas.The output will deactivate when any fire or zone alarm occu

Seite 20

25SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA PGM OUTPUTSPGM OUTPUTSPGM OUTPUTSPGM OUTPUTSPGM OUTPUTSThis output w

Seite 21

26SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA PGM OUTPUTSPGM OUTPUTSPGM OUTPUTSPGM OUTPUTSPGM OUTPUTSThis output w

Seite 22 - Links Module

27The output will deactivate when any alarm occurs on any of the selected areas. The output will staydeactivated until the area that caused the alarm

Seite 23 - Main Bell Output

1Using PC6010 ManualsThere are 3 main manuals for PC6010 installers:• System Manual• Programming Manual• Programming WorksheetsBefore beginning your i

Seite 24 - PGM Outputs

28SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA EVENT SCHEDULINGEVENT SCHEDULINGEVENT SCHEDULINGEVENT SCHEDULINGEVEN

Seite 25 - PGM Pulse Times

29SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA EVENT SCHEDULINGEVENT SCHEDULINGEVENT SCHEDULINGEVENT SCHEDULINGEVEN

Seite 26 - Programmable Output Options

30SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA EVENT SCHEDULINGEVENT SCHEDULINGEVENT SCHEDULINGEVENT SCHEDULINGEVEN

Seite 27

31Holiday Groups allow for exceptions to the regular date schedule. There are four Holiday Groups. Up to twoyears of dates can be programmed per holid

Seite 28

32Arming/disarming schedules are used to auto arm or auto disarm area(s) according to the selected dateschedule. There are 50 Arm/Disarm schedules.The

Seite 29

33The PC6820 Access Control module allows the PC6010 have access control of up to 32 doors. EachPC6820 is capable of controlling 2 access card readers

Seite 30 - Event Scheduling

34Unlock Door on Request To Exit?YES = A Request To Exit will cause the door to unlock for the programmed Door Unlock Time. The LEDoutput will activat

Seite 31

35Arm Disable?YES = When all areas assigned in the PC6820 Arm/Disarm Mask are armed, the reader will be disabled.The LED will not function and access

Seite 32

36Select a date schedule to determine at what times the selected areas may be armed by a user presentingtheir access card at the appropriate reader. O

Seite 33

37AREA SECTIONAREA SECTIONAREA SECTIONAREA SECTIONAREA SECTION ADADADADADD/D/D/D/D/EDIT AREAEDIT AREAEDIT AREAEDIT AREAEDIT AREA

Seite 34

2The PC6010 Installer’s Programming is broken down into 5 major sections:System Section: You will find programming options which affect the operation

Seite 35 - PC6820 Options

38AREA SECTIONAREA SECTIONAREA SECTIONAREA SECTIONAREA SECTION ADADADADADD/D/D/D/D/EDIT AREA EDIT AREA EDIT AREA EDIT AR

Seite 36

39Zone AssignmentThis section is for assigning type and options for each individual zone.By default, the first 16 zones on the main panel are assigned

Seite 37

40AREA SECTIONAREA SECTIONAREA SECTIONAREA SECTIONAREA SECTION ADADADADADD/D/D/D/D/EDIT AREA EDIT AREA EDIT AREA EDIT AREA

Seite 38

41AREA SECTIONAREA SECTIONAREA SECTIONAREA SECTIONAREA SECTION ADADADADADD/D/D/D/D/EDIT AREA EDIT AREA EDIT AREA EDIT AR

Seite 39 - Area Section

42A 24 Hour Medical zone is armed at all times, and will create an alarm when violated if the Area is armedor disarmed.When armed, if violated, this z

Seite 40 - Area Times

43DELETE AREADELETE AREADELETE AREADELETE AREADELETE AREA(1)(1)(1)(1)(1)COPY AREACOPY AREACOPY AREACOPY AREACOPY AREA(2)(2)(2)(2)(2)YES = The reportin

Seite 41 - Zone Assignment

44BACKBONE SECTIONBACKBONE SECTIONBACKBONE SECTIONBACKBONE SECTIONBACKBONE SECTION ORIGINATOR IDORIGINATOR IDORIGINATOR IDORIG

Seite 42 - Zone Type

45MODULE HARDWAREMODULE HARDWAREMODULE HARDWAREMODULE HARDWAREMODULE HARDWARE COMBUS MODULE/BACKBONE MODULECOMBUS MODULE/BACKB

Seite 43

46EVENT BUFFEREVENT BUFFEREVENT BUFFEREVENT BUFFEREVENT BUFFER PRINT BUFFERPRINT BUFFERPRINT BUFFERPRINT BUFFERPRINT BUFFERDIA

Seite 44 - Zone Options

47Appendix AList of Available ASCII CharactersNOTE: Characters 000 - 007 are language dependent.096112176097113161177098114162178192193194099115163179

Seite 45 - Delete/Copy Area

3SYSTEM RESETSYSTEM RESETSYSTEM RESETSYSTEM RESETSYSTEM RESET(2)(2)(2)(2)(2)SYSTEM SECTION SYSTEM SECTION SYSTEM SECTION SYSTEM SECTION SYSTEM SECTION

Seite 46 - Backbone Section

Appendix BReporting CodesNotes on Contact IDThe following is a list of Contact ID reporting codes. The firstdigit (in parentheses) will automatically

Seite 47 - Module Hardware

Reporting Code Code Sent When...DialerDirection*RecommendedContact IDSIA Auto RepCodes**Periodic Test periodic test transmission Other (6) A2 RP-000Bu

Seite 48 - Diagnostics

©2000 Digital Security Controls Ltd.Toronto, Canadawww.dscgrp.comPrinted in Canada 29004812 R001

Seite 49 - Appendix A

4SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA SYSTEM OPTIONSSYSTEM OPTIONSSYSTEM OPTIONSSYSTEM OPTIONSSYSTEM OPTION

Seite 50 - Appendix B

5SYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREASYSTEM AREA SYSTEM OPTIONSSYSTEM OPTIONSSYSTEM OPTIONSSYSTEM OPTIONSSYSTEM OPTION

Seite 51 - Zone Reporting Codes

6The system uses the Public key, together with the programmed Private key, to encrypt communicationsover the Combus, making them more secure. The Publ

Seite 52 - Toronto, Canada

7PERIODIC CALLUPPERIODIC CALLUPPERIODIC CALLUPPERIODIC CALLUPPERIODIC CALLUP(1)(1)(1)(1)(1)SET CYCLE DAYSSET CYCLE DAYSSET CYCLE DAYSSET CYCLE DAYSSET