
Programming Sections: 5.13 Bell Options
29
PGM output options [01], [03], [05]-[08], [11]-[22] have the fol-
lowing attributes:
PGM attributes return to their default settings when you change
PGM output options. Please see the programming worksheets
for a list of the default settings for each PGM output type.
Care should be taken in selecting the normal and active states of
each PGM output to ensure that an undesirable output state
does not occur after a loss and restore of AC power.
NOTE:
Attribute [3] must be ON (default) for PGM output
options [16].
If you program more than one PGM output as the same output
type (e.g. If PGM1 and PGM2 are both programmed as [19]
Command Output 1), the settings for output attributes [1], [2]
and [5] must be the same. This does not apply to outputs pro-
grammed as types [09] and [10].
Assigning Partitions to Programmable Outputs
By default, all programmable outputs are assigned to partition 1.
To allow programmable outputs to work on other partitions,
enable or disable the appropriate partitions in the Partition
Assignment programming sections.
PGM Output Attributes . . . . . . . . . . . . . . Sections [501] - [514]
PGM Output Partition Assignment . . . . . . Sections [551] - [564]
PGM Output timer. . . . . . . . . . . . . . . . . . . . . . . . Section [170]
5.13 Bell Options
The siren will silence after the number of minutes programmed
for the Bell Cut-off time have passed.
The panel supervises the Bell output. If an open condition is
detected, the panel will immediately indicate a trouble condition
by beeping the keypad twice every 10 seconds to alert the owner
of the problem. The panel can send a Bell Circuit Trouble and
Trouble Restoral reporting codes to indicate the situation (see
section 5.8
“Communicator - Reporting Codes”
on page 25).
If the Temporal Three Fire Signal option is enabled, all Fire sig-
nals will follow the Temporal Three Pattern as described in NFPA
72. If turned OFF all Fire signals will sound a one second on, one
second off cadence.
If Fire Bell Continuous is enabled, the alarm output will sound
until a code is entered. If disabled, the alarm will sound until a
code is entered or the bell cut-off time has expired.
NOTE:
Only fire zones will follow the Temporal Three Fire
Signal.
Bell Cut-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section [005]
Bell Circuit Trouble Reporting Code . . . . . . . . . . . Section [349]
Bell Circuit Trouble Restoral Reporting Code . . . . Section [350]
Temporal Three Fire Signal
Enable/Disable. . . . . . . . . . . . . . . . . . .Section [013], Option [8]
Fire Bell Continuous . . . . . . . . . . . . . .Section [014], Option [8]
5.14 Fire, Auxiliary, and Panic Keys
The emergency keys are available on all keypads. These keys
must be pressed and held for 2 seconds before they will activate.
This 2 second delay is designed to help prevent accidental activa-
tion.
If the Fire Keys option is enabled, when the Fire keys are pressed
and held for 2 seconds, the panel will activate the alarm output.
It pulses one second on, one second off only if option 8 of Sec-
tion [013] is disabled (Standard Fire option). If Fire Bell Continu-
ous is selected the alarm output will sound until a code is
entered, otherwise it will sound until a code is entered or the
alarm output times out. Communication of the signal to central
station is immediate.
If the Auxiliary Keys are pressed and held for 2 seconds the
panel will sound the keypad beeper three times to verify activa-
tion. The panel will beep the keypad ten times rapidly to verify
communication to the central station.
If the Panic Keys are pressed and held for 2 seconds, the panel
will immediately communicate the signal to central station. If
Panic Keys Audible is enabled, the panel will beep the keypad
three times upon activation and activate the alarm output until a
code is entered or the alarm output times out. Otherwise the
alarm will be completely silent.
NOTE:
The Fire, Auxiliary, Panic keys will operate even if
Keypad Blanking and Keypad Lockout are active (see sec-
tion 5.20
“Keypad Options”
on page 31).
NOTE:
Fire, Auxiliary, and Panic key transmissions follow
the partition 1 alarm/restore call direction options (see sec-
tion 5.4
“Communicator - Dialing”
on page 22).
Fire Keys Enable . . . . . . . . . . . . . . . . .Section [015], Option [1]
Panic Keys Audible . . . . . . . . . . . . . . .Section [015], Option [2]
Fire Bell Continuous . . . . . . . . . . . . . .Section [014], Option [8]
5.15 Arming and Disarming Options
If the Arm/Disarm Bell Squawk option is enabled the panel will
squawk the alarm output once upon arming and twice upon dis-
arming. If an alarm is in memory, when the panel is disarmed the
bell will sound three pairs of disarm squawks.
NOTE:
If you enable the Bell Squawk on Arming/Disarming
(section [014], option [1]), the bell will sound arm/disarm
bell squawks for all access codes, regardless of the pro-
gramming for attribute [7] (see section 4.1
“Access Codes”
on page 13).
Enable both the Squawk on Away Arming/Disarming Only
and the Arm/Disarm Bell Squawk options to have the panel
squawk the bell only when the system is away armed or dis-
armed.
If the Opening After Alarm Keypad Ringback option is turned
on, the system will beep the keypad 10 times rapidly if the panel
is disarmed after an alarm occurred. If the Opening After
Attribute ON OFF
[1]-[2] For future use
[3] True Output: The out-
put energizes when acti-
vated (except for Option
[03] Sensor Reset).
Inverted Output: The
output will de-energize
when activated.
[4] 5 Second Pulse: The
output will activate once
for 5 seconds (by
default) when initiated
by the user.
Output ON/OFF: The
output will turn ON and
OFF when initiated by
the user (only applicable
to options [19] to [22]).
NOTE: The
pulse timer
can be changed in Pro-
gramming Section [170]
[5] Access Code Req.:
The output requires a
code for activation.
No Code Req.: No code
required. (only applicable
to keypad-activated out-
puts)
Kommentare zu diesen Handbüchern