Seitenansicht 34
33
The PC6820 Access Control module allows the PC6010 have access control of up to 32 doors. Each
PC6820 is capable of controlling 2 access card readers (one for each door) and a total of 16 modules may
be enrolled on the system. Each door can have some or all of the 1000 users enabled to arm or disarm the
assigned area(s).
This section describes all the programming options for the PC6820. For PC6820 wiring, specifications,
and a more detailed description of how the PC6820 works, please see the PC6820 Installation Manual.
The following options are provided for each module.
Terms used in this section:
REX Request To Exit - This input of the PC6820 when activated will unlock the door for the
duration of the Door Unlock Time.
Post Postpone Arm - When enabled this PC6820 input will delay the autoarm of the PC6010
for the selected areas for the programmed time.
Arm Arm Request - this input of the PC6820 will allow the selected areas to be armed when a
valid access card has been used.
Lock This output of the PC6820 will provide power to the locking device used to control access
to a given area of the system.
Door A zone input that may be assigned to any area on the system. This door input will then be
an active part of the alarm system.
Reader A device used to read the identification number of an access card.
Door Forced This event is generated when a door controlled by a PC6820 zone is opened
Open without a REX activation or valid user card first being used.
Failsoft On This event is logged to the event buffer by the PC6820 as an indication that the module has
gone into stand alone mode. When the panel loses communication to the module (PC6010
is powered down for example) the PC6820 will still be able to function. All events that occur
will be stored by the PC6820 and when communication is restored to the module, the
events will be sent to the PC6010.
Failsoft Off This event is logged when Combus communication is restored to the module
Window (inside of window/outside of window) - These terms are used when describing when a
schedule is active (inside of window) or when the schedule time has expired (outside of
window)
The PC6820 is capable of supporting different types of access card readers. The same type of reader must be
used on both doors of an access card module but different modules may use different reader types. This data
entry section will allow a reader type to be assigned to the selected PC6820.
Supported Reader Types:
00 - Polaris 1- Magnetic card reader. 7 Digits with clock and data.
01 - Shadow-Prox - Extended range proximity reader SH5, SH6, SH7, SH-VR 32 Bits.
02 - 26 Bit Standard Wiegand
Default access card reader is 00 (Polaris 1).
This section contains the programming for the selected PC6820. Each PC6820 contains two doors (Door
#1 and Door #2) each with independent programming abilities. The following is a description of the
features for each door.
Door Lock Reversed?
YES = Power (13.85V) will be applied to the locking device to keep the door closed. The Lock will
deactivate when a valid access card is used to open the door. This option is dependent on the type
of locking device being used. Check the installation sheet provided with the locking device to see
what is required for power.
NO = Power will be applied to unlock the door. For use with Fail Secure devices such as Electronic Door
Strike.
Default Condition is NO.
PC6820 Options
SYSTEM AREASYSTEM AREA
SYSTEM AREASYSTEM AREA
SYSTEM AREA
6820 OPTIONS6820 OPTIONS
6820 OPTIONS6820 OPTIONS
6820 OPTIONS
READER TYPEREADER TYPE
READER TYPEREADER TYPE
READER TYPE
(0)(0)
(0)(0)
(0)
DOOR DEFINITIONDOOR DEFINITION
DOOR DEFINITIONDOOR DEFINITION
DOOR DEFINITION
(1)(1)
(1)(1)
(1)
SELECT DOOR 1-2SELECT DOOR 1-2
SELECT DOOR 1-2SELECT DOOR 1-2
SELECT DOOR 1-2
(1) - (2)(1) - (2)
(1) - (2)(1) - (2)
(1) - (2)
TOGGLE OPTIONSTOGGLE OPTIONS
TOGGLE OPTIONSTOGGLE OPTIONS
TOGGLE OPTIONS
(00)(00)
(00)(00)
(00)
LOCK REVERSED?LOCK REVERSED?
LOCK REVERSED?LOCK REVERSED?
LOCK REVERSED?
NN
NN
N
6820 OPTIONS6820 OPTIONS
6820 OPTIONS6820 OPTIONS
6820 OPTIONS
(08)(08)
(08)(08)
(08)