DSC PC6010 Installationshandbuch Seite 50

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 52
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 49
Appendix B
Reporting Codes
Notes on Contact ID
The following is a list of Contact ID reporting codes. The first
digit (in parentheses) will automatically be sent by the control.
The last two digits are programmed to indicate specific
information about the signal.
For example, if zone 1 is an entry/exit point, the alarm reporting
code could be programmed as [34]. The central station would
receive the following:
*BURG - ENTRY/EXIT - 1
In the above example, the “1” indicates the zone in alarm.
Notes on SIA Format
If the SIA 1 Account # option is selected, the panel will send
the system account code along with its data transmission (ref #
[000401], scroll to option). At the receiver, the transmission
would look similar to this example:
N Ri01 / BA 001
N = New Event
Ri01 = Partition /Area Identifier
BA = Burglary Alarm
001 = Zone 1
Table 1:
Reporting Codes
Reporting Code Code Sent When...
Dialer
Direction*
Recommended
Contact ID
SIA Auto Rep
Codes**
Zone Alarms zone goes into alarm A/R
see Table 2 “Zone Reporting Codes”
Zone Restorals alarm condition has been restored A/R
Zone Trouble/Tamper zone exhibits a trouble/tamper condition A/R
Zone Trouble/Tamper Rest. trouble/tamper condition has cleared A/R
Zone Fault zone exhibits a zone fault A/R
Zone Fault Rest. zone fault condition has cleared A/R
Module Tamper Alarm/Rest.
enrolled module has a tamper alarm/tamper is
restored
A/R (1) 45 TA-000/TR-000
Closings area armed (user 001-128 indicated) O/C (4) A2 CL-UUU
Closing 129-1000 user code # 129-1000 used to arm partition O/C (4) A2 CL-UUU
Partial Closing
one or more zones intentionally bypassed
when area armed
O/C (4) 56 CW-000
Automatic (Scheduled) Closing auto arming according to schedule O/C (4) A3 CA-000
Auto Arm Cancellation auto arm cancelled O/C (4) A5 CE-000
6442 APS Closing area armed by APS software O/C (4) A2 CL-000
6443 ODS Closing area armed by ODS software O/C (4) A2 CL-000
Keypad Lockout
max. number of incorrect access codes has been
entered at a keypad
Other (4) 21 JA-000
Openings area disarmed (user 001-128 indicated) O/C (4) A2 OP-UUU
Opening 129-1000 user code # 129-1000 used to disarm area O/C (4) A2 OP-UUU
Opening After Alarm area disarmed with alarm in memory O/C (4) A6 OR-000
Automatic (Scheduled) Opening auto disarming according to schedule O/C (4) A3 OA-000
6442 APS Opening area disarmed by APS software O/C (4) A2 OP-000
6443 ODS Opening area disarmed by ODS software O/C (4) A2 OP-000
Battery Trouble/Rest. PC6010 battery is low Other (3) A2 YT-000/YR-000
AC Line Trouble/Rest.
AC power to control panel is disconnected or
interrupted
Other (3) A1 AT-000/AR-000
Main Bell Trouble/Rest. open circuit detected across bell terminals Other (3) 21 YA-000/YH-000
Main Auxiliary Trouble/Rest. aux voltage supply trouble Other (3) AA YP-000/YQ-000
Combus Fault/Rest.
control panel loses communications with
connected module(s)
Other (3) 33 ET-000/ER-000
Combus Low Power/Rest.
a module connected to the Combus has low
power
Other (3) 33 ET-000/ER-000
Backbone Trouble/Rest.
control panel loses communications with
connected backbone module(s)
Other (3) 33 ET-000/ER-000
TLM Failure/Rest.
telephone line monitoring trouble (sent via
LINKS or when land line communications
resume)
Other (3) 51 LT-000/LR-000
FTC Restoral
control panel has restored communications to
central station (after TLM Fail)
Other (3) 54 YK-000
* A/R = alarms/restorals; O/C = openings/closings
** PPP = partition number; UUU = user number (user 1000=999); ZZZ = zone number